1 / 3
EnergyPlus
Current Booster Board (3-Channel, 0–10 V)
SKU: EPL-CBS
A 3-channel buffer board that boosts a 0–10 V control signal to 100 mA per channel without changing its voltage.
Price on Request
● Out of StockPlease contact us for pricing on this product.
Description
The analog outputs of PLCs and controllers are limited to a low current; when you want to drive several actuators, or a load that draws more current, from the same 0–10 V signal, the output struggles. The EPL-CBS is a 3-channel current booster board that acts as a buffer between the control system and the load. Built on a common-collector (emitter follower) stage, it raises the current capacity to 100 mA per channel without changing the signal voltage, and protects the control output from overloading by separating it from the load.
KEY FEATURE
A 3-channel 0–10 V buffer board that boosts current without changing voltage and drives loads safely.
ADVANTAGES
• Protects the control output — The buffer stage separates the PLC or controller output from the load, so the output is not affected by excessive current draw.
• Three independent channels — Three separate signals are boosted on one board without interfering with each other, saving wiring and panel space.
• The signal stays the same — Unity-gain design: 0–10 V in, 0–10 V out; only the available drive current increases.
TECHNICAL SPECIFICATIONS
Country of origin: Türkiye
Supply voltage: 230 VAC, 50/60 Hz
Power consumption: 3.2 VA
Channels: 3 (IS_1–IS_3 inputs, OS_1–OS_3 outputs)
Input voltage range: 0 – 10 VDC · Max input current: 20 mA (per channel)
Output voltage range: 0 – 10 VDC · Max output current: 100 mA (per channel)
Indicator: POWER LED (supply)
Terminals (left to right)
Chassis earth · ~ ~ (230 VAC) — 0V · IS_1 · IS_2 · IS_3 — 0V · OS_1 · OS_2 · OS_3
0V: common GND for inputs and outputs
Environment and dimensions
Operating temperature: -10 °C … +45 °C · Relative humidity: ≤ 90% (non-condensing)
Ingress protection: IP20
Dimensions: 42 × 85 × 32 mm · Weight: 250 g
Mounting: inside a panel or enclosure, screwed to a wall or mounting plate
SCOPE OF DELIVERY
1 × EPL-CBS
INSTALLATION NOTES
• The board is for use inside a panel; in industrial or outdoor locations, mount it in a panel or enclosure rated at least IP54–IP65.
• Wire it with the power off; observe the 0V / input / output terminals and make sure no bare conductor touches a metal surface.
• Do not clamp metal fixings directly onto the board's heat-shrink sleeve, and leave space around it for heat to escape.