Duct Temperature Sensor NTC 20K (Passive)
SKU: EPL-DT-20
Passive NTC 20K duct temperature sensor with ABS housing and Ø6 mm stainless steel probe, for AHU supply, return and fresh air.
Price on Request
● Out of StockPlease contact us for pricing on this product.
Description
Passive NTC 20K sensor for measuring supply, return and fresh air temperature in air ducts and air handling units. Combined with an EPL-SS stainless steel sensor well it can also be used as an immersion sensor on pipework. Connects directly to the NTC 20K inputs of DDC, PLC and fan-coil controllers.
KEY FEATURES
• TDK (EPCOS) NTC 20 kΩ element, R25 tolerance ±1 % (≈ ±0.2 K at 25 °C)
• Ø6 mm stainless steel probe, epoxy filled
• ABS housing with PG7 cable gland, screw terminals (0.5 … 2.5 mm²), IP67
• Quick mounting on the duct wall with 2 screws; a rubber seal closes the hole airtight
• Passive, 2-wire, non-polarised: no power supply needed
PROBE LENGTH OPTIONS
• 100 mm — matching well EPL-SS-100
• 150 mm — matching well EPL-SS-150
Please state the probe length when ordering. Choose the 150 mm probe for wide ducts.
TECHNICAL SPECIFICATIONS
Sensing element: NTC thermistor, epoxy-coated disc (TDK EPCOS)
Resistance: R25 = 20 kΩ · B25/100 = 4300 K (R/T curve 2904)
Tolerance: R25 ±1 % → ≈ ±0.2 K @ 25 °C
Operating temperature: −30 … +80 °C (element −55 … +155 °C)
Measuring current: ≤ 0.1 mA (recommended)
Self-heating: ≈ 4 mW/K (element) → ≈ 0.05 K at 0.1 mA
Output: Passive resistance, 2-wire, non-polarised
Connection: 2-pole screw terminal, 5.0 mm, PA66 UL 94 V-0
Wire size / strip length: 0.5 … 2.5 mm² / 8 mm · tightening torque 0.5 N·m
Cable gland: PG7
Probe: Stainless steel, Ø 6 mm, epoxy filled
Probe length: 100 / 150 mm
Housing: ABS
Mounting: 2 screws on the duct surface
Weight (ready to install): 67 g
Degree of protection: IP67 (EN 60529)
Environment: Non-condensing
Protection class: III — safety extra-low voltage (SELV/PELV) circuits only
Element approval: UL (E69802)
Conformity: CE · WEEE 2012/19/EU (not household waste)
RESISTANCE VALUES (EXAMPLES)
0 °C: 71,126 Ω · 25 °C: 20,000 Ω · 50 °C: 6,673 Ω · 70 °C: 3,061 Ω
Thanks to the high resistance of NTC 20K, cable resistance has very little effect: even on a 100 m run of 2 × 0.5 mm² the error is only −0.01 K at 25 °C, so no offset correction is normally needed.
WIRING AND INSTALLATION
• On the controller, set the NTC 20K input to the B25/100 = 4300 K curve. The common "NTC 20K B3950" curve is different; selecting it can shift the reading by 1.5–2 °C.
• Drill a hole in the duct wall sized for the rubber seal; the probe tip should sit in the middle third of the duct cross-section.
• Fix the housing to the duct with 2 screws, with the PG7 gland facing down. Strip the wires 8 mm, connect them to the terminal (0.5 N·m) and tighten the gland to seal the cable entry.
• Do not mount directly downstream of heating or cooling coils or humidifiers; choose a point where the air is fully mixed.
• For pipework (water) applications, use it together with an EPL-SS well of the matching length.
• Connect the sensor only to the low-voltage sensor input of a controller; never connect it to 230 V mains. Wiring must be done by qualified personnel with the power off; do not run the sensor cable in the same duct or conduit as 230 V power cables.
SCOPE OF DELIVERY
1 × sensor, 2 × mounting screws and wall plugs