📞 02129099810
EnergyPlus
← Back to Products
1 / 2

EnergyPlus

Room Temperature Sensor NTC 20K (Passive)

SKU: EPL-MT-20

Passive NTC 20K room temperature sensor with 80 × 80 mm ABS housing and push-in terminals, for DDC, fan-coil and VRF controllers.

Price on Request

● Out of Stock

Please contact us for pricing on this product.

Description

Passive NTC 20K sensor for measuring indoor air temperature. Connects directly to the NTC 20K inputs of DDC, PLC, fan-coil and VRF controllers and mounts on the wall or on a flush-mounting box. KEY FEATURES • TDK (EPCOS) NTC 20 kΩ element, R25 tolerance ±1 % (≈ ±0.2 K at 25 °C) • Screwless push-in terminal, 0.2 … 1.5 mm² — fast and reliable wiring • Ventilation slots on all four sides, rear cable entry • Clean 80 × 80 × 21 mm ABS housing; wall or flush-box mounting • Passive, 2-wire, non-polarised: no power supply needed TECHNICAL SPECIFICATIONS Sensing element: NTC thermistor, epoxy-coated disc (TDK EPCOS) Resistance: R25 = 20 kΩ · B25/100 = 4300 K (R/T curve 2904) Tolerance: R25 ±1 % → ≈ ±0.2 K @ 25 °C Measuring range: 0 … +50 °C (room) Measuring current: ≤ 0.1 mA (recommended) Self-heating: ≈ 4 mW/K (element) → ≈ 0.05 K at 0.1 mA Output: Passive resistance, 2-wire, non-polarised Terminal: 2-pole push-in, 5.08 mm, PA66 UL 94 V-0 Wire size / strip length: 0.2 … 1.5 mm² (AWG 22 … 16) / 9 mm Withstand voltage (terminal): AC 2500 V / 1 min Housing: ABS, UL 94 HB; heat deflection (HDT) 85 °C Dimensions (W × H × D): 80 × 80 × 21 mm Mounting: Wall (4 screws) or flush-mounting box Cable entry: From the rear of the base Weight: 34.65 g Operating environment: 0 … +50 °C, dry indoor, non-condensing Degree of protection: IP30 (EN 60529) Pollution degree / overvoltage category: 2 / III Terminal approvals: UL (cURus), VDE, CQC · RoHS compliant Protection class: III — safety extra-low voltage (SELV/PELV) circuits only Element approval: UL (E69802) Conformity: CE · WEEE 2012/19/EU (not household waste) RESISTANCE VALUES (EXAMPLES) 0 °C: 71,126 Ω · 20 °C: 25,366 Ω · 25 °C: 20,000 Ω · 30 °C: 15,884 Ω Thanks to the high resistance of NTC 20K, cable resistance has very little effect: even on a 100 m run of 2 × 0.5 mm² the error is only −0.01 K at 25 °C, so no offset correction is normally needed. WIRING AND INSTALLATION • On the controller, set the NTC 20K input to the B25/100 = 4300 K curve. The common "NTC 20K B3950" curve is different; selecting it can shift the reading by 1.5–2 °C. • Separate the cover from the base and feed the cable through the rear entry; mount the base flat on the wall or a flush box with 4 screws. • Seal the cable entry and the conduit opening; air coming from inside the wall falsifies the reading. • Strip the wires 9 mm and push them into terminals 1–2 (use ferrules on stranded wire), then fit the cover. • Mount about 1.5 m above the floor on an inner wall; avoid direct sun, radiators, air outlets, door/window areas and outside walls. • Connect the sensor only to the low-voltage sensor input of a controller; never connect it to 230 V mains. Wiring must be done by qualified personnel with the power off; do not run the sensor cable in the same duct or conduit as 230 V power cables. SCOPE OF DELIVERY 1 × sensor