1 / 2
EnergyPlus
Water Leak Detector (Point-Type Sensor)
SKU: EPL-WDS
Water leak detector with a point-type sensor: built-in buzzer, adjustable alarm delay and a dry-contact relay output for BMS/PLC.
Price on Request
● Out of StockPlease contact us for pricing on this product.
Description
Water leaks are among the faults that grow unnoticed and cost a building the most. The EPL-WDS reacts the moment water first collects in the monitored area and reports the leak while it is still small. Water is detected by a point-type sensor on the S1–S2 input; the unit sounds its built-in buzzer and signals a building management system (BMS), PLC or alarm panel through its dry-contact relay output.
KEY FEATURE
Point-type water leak detection with a local audible alarm and a relay output that connects straight to automation.
ADVANTAGES
• Early warning, limited damage — The sensor sits at the lowest point, in full contact with the floor, so the leak is reported before it can damage the structure or electrical equipment.
• Direct integration into automation — The changeover (SPDT) dry-contact output (COM / NO / NC) works with BMS, PLCs and alarm panels without any extra converter.
• Delay against false alarms — The alarm delay is set with a trimmer between 0 and 30 seconds, so brief splashes do not raise an alarm.
TECHNICAL SPECIFICATIONS
Country of origin: Türkiye
Supply voltage: 24 VDC ±5%
Power consumption: 0.6 W / 25 mA @ 24 VDC
Relay output: 1 × changeover (SPDT) dry contact — COM / NO / NC
Contact rating: 1 A @ 120 VAC · 1 A @ 24 VDC (resistive load)
Alarm delay: 0 – 30 s (adjustable by trimmer)
Indicators: POWER LED (supply), OUTPUT LED (water detected / relay energised)
Audible alarm: built-in buzzer (while the alarm is active)
Sensor: point type, two-wire, non-polarised (S1, S2)
Cables: sensor cable 50 cm · supply and relay cable 50 cm
Environment and dimensions
Operating temperature: -10 °C … +45 °C · Storage: -20 °C … +70 °C
Relative humidity: 10 … 90% (non-condensing) · Ingress protection: IP64
Dimensions: 57 × 48 × 41 mm · Weight: 200 g
Mounting: wall mounting (2 screws and wall plugs)
CONNECTIONS
S1, S2 (black / yellow): point-type water sensor
24V, 0V (red / blue): 24 VDC supply
COM (white), NC (yellow), NO (green): relay output — use COM–NO if the automation system expects a contact that closes on alarm, COM–NC if it expects one that opens.
SCOPE OF DELIVERY
1 × EPL-WDS · 1 × point-type water sensor (50 cm cable) · 1 × supply and relay cable (50 cm) · 2 × mounting screws and wall plugs
INSTALLATION NOTES
• Fix the unit above the highest expected water level, within reach of the sensor cable; place the sensor flat on the floor, or vertically on the wall with its contacts touching the floor.
• To test, bridge the sensor contacts with a damp cloth for longer than the set delay: the OUTPUT LED should light, the buzzer should sound and the alarm should reach the automation system.